| Required Active Chemical Mass |
Active mass rate (g/h) = Water flow (m³/h) × Chemical concentration (mg/L)
|
10 m³/h × 2 mg/L
|
20 g/h of active chemical |
| Required Chemical Solution Flow |
Solution flow (L/h) = Active mass rate (g/h) ÷ [Solution strength (decimal) × Density (kg/L) × 1,000]
|
20 ÷ (0.10 × 1.05 × 1,000)
|
0.190 L/h, or approximately 190 mL/h |
| Example: Low-Flow Water Treatment |
Select a pump using the calculated solution flow and the actual discharge pressure.
|
Water flow: 10 m³/h
Target: 2 mg/L active
Stock solution: 10% w/w
Density: 1.05 kg/L
|
Calculated dosing rate: 190 mL/h
Suggested rated capacity: approximately 230–240 mL/h when a 20% design margin is applied
|
| Example: Boiler-Water Treatment |
Use the same mass-balance method, but confirm the chemical supplier’s required active concentration.
|
Water flow: 4 m³/h
Target: 5 mg/L active
Stock solution: 5% w/w
Density: 1.02 kg/L
|
Active chemical: 20 g/h
Solution flow: approximately 0.392 L/h
With 20% margin: approximately 0.47 L/h rated capacity
|
| Discharge Pressure |
Required pump pressure = Process pressure + Static head pressure + Friction losses + Injection-point backpressure
|
Process pressure: 4.0 bar
Pipe and valve losses: 0.6 bar
Injection assembly allowance: 0.4 bar
|
Minimum calculated pressure: 5.0 bar
Select a pressure rating above the calculated operating value
|
| Pressure Conversion |
1 bar = 100 kPa ≈ 14.5 psi
For water near ambient temperature, 1 bar corresponds to approximately 10.2 m of water head.
|
5.0 bar × 100 kPa/bar
5.0 bar × 14.5 psi/bar
|
500 kPa or approximately 72.5 psi
|
| Pump Capacity Margin |
Rated capacity should normally exceed the calculated maximum dosing rate to allow for calibration variation, wear, temperature changes, and future adjustment.
|
Calculated maximum: 0.392 L/h
Design margin: 20%
|
Minimum rated capacity: 0.392 × 1.20 = 0.470 L/h
|
| Turndown Requirement |
Turndown ratio = Maximum required flow ÷ Minimum required flow
|
Maximum flow: 0.470 L/h
Minimum flow: 0.047 L/h
|
Required turndown ratio: 10:1
|
| Pump Type Selection |
Match the pump design to flow range, pressure, chemical compatibility, accuracy, and control method.
|
Continuous metering at low-to-medium flow and moderate pressure
|
Metering pumps with adjustable stroke, speed, or pulse control are commonly suitable; verify the actual performance curve.
|
| Chemical Compatibility |
Check wetted materials against concentration, temperature, viscosity, vapor pressure, and chemical reactivity.
|
Sodium hypochlorite, acids, alkalis, oxidizers, and solvents may require different diaphragm, valve, seal, and tubing materials.
|
Use the chemical safety data sheet and material-compatibility data before finalizing the pump.
|
| Injection-Point Check |
The pump must overcome the pressure at the injection point. A check valve or injection valve may be required to prevent backflow.
|
Process pressure at injection point: 4.0 bar
|
Do not size the pump from tank elevation alone; verify actual line pressure and injection-valve resistance.
|
| Calibration Verification |
Measured flow (L/h) = Collected volume (L) ÷ Collection time (h)
|
Collected volume: 0.250 L
Collection time: 0.5 h
|
Measured dosing rate: 0.500 L/h
|
| Control and Monitoring |
Select control inputs according to the process: manual setting, pulse signal, 4–20 mA signal, flow-paced control, or feedback from an analyzer.
|
Water flow varies from 5 to 10 m³/h while the target concentration remains constant.
|
Flow-paced control can adjust chemical dosing in proportion to the changing water flow.
|
| Final Selection Checklist |
Confirm flow range, pressure rating, chemical compatibility, temperature rating, turndown, control signal, calibration method, and safety accessories.
|
Design point: 0.470 L/h maximum at 5.0 bar minimum operating pressure
|
Choose a pump whose documented operating curve covers the complete required flow-pressure range.
|