ESSCO Pumps and Controls

777 Motor Saver

SKU: 777MotorSaver
Weight: 5 lbs
777 Motor Saver 082809 More details...
Price: $602.56
777 Motor Saver
Previous Item   Next Item
 
Product Details

 

Input Voltage 200-480VAC, 3Ø (Standard)
(500-600VAC, 3Ø Available)
Frequency 50 or 60Hz
Motor Full Load amp Range 2-90 Amps, 3Ø (Direct)
91-800 Amps, 3Ø (External CT's)
Programmable Operating Points
LV - Low Voltage Threshold * 170V (450V*) - HV Setting
HV - High Voltage Threshold * LV Setting - 528V (660V*)
VUB - Voltage Unbalance Threshold 2-15% or 999 = Off
MULT - # of Loops or CT Ratio (XXX:5) 1-10 Loops or 100-800 Ratio
OC - Over Current Threshold (20-100A) / MULT
UC - Under Current Threshold (0, 10-98A) / MULT
CUB - Current Unbalance Threshold 2-25% or 999 (OFF)
TC - Over Current Trip Class ** 5, J5, 10, J10, 15,
J15, 20, J20, 30, J30
RD1 - Rapid Cycle Timer 0-500 Seconds
RD2 - Restart Delay After All Faults Except Under Current (Motor Cool Down Timer) 2-500 Minutes
RD3 - Restart Delay After Under Current (Dry Well Recovery Timer) 2-500 Minutes
#RU - Number of Restarts After Under Current 0, 1, 2, 3, 4, A (Automatic)
ADDR - RS485 Address A01-A99
#RF - Number of Restarts After All Faults Except Under Current *** 0, 1, oc1, 2, oc2, 3,
oc3, 4, oc4, A, ocA
UCTD - Under Current Trip Delay 2-60 Seconds
GF - Ground Fault Current Threshold (3-20A) / MULT or OFF
Specifications
Low Voltage 4 seconds
Output Contact Rating
(Pilot Duty) SPDT
480VA @ 240VAC
Transient Protection (Internal) 2500 V for 10 mSeconds
Accuracy
Voltage ±1%
Current ±3% ( <100 amps direct)
Timing 5% ±1 Second
Repeatability
Voltage ±0.5%
Current ±1% ( <100 amps direct)
Temperature Range 0 to 70°C
Physical Specifications
Dimensions 3.0" H x 5.1" D x 3.6" W
Power Consumption 10 Watts (Max.)
Weight 1.2 lbs.
NOTES: SymCom's 777-LR & 777-MV can be programmed prior to installation by applying 115 VAC between the L1 and L2 terminals.
* 575 volt Model (MS 777-575)
** If J prefix is displayed in trip class setting, jam protection is enabled.
*** If "oc" is enabled in the #RF setting, the Over Current will be included as a normal fault and the relay will automatically restart after RD2 expires, otherwise, manual reset is required after an Over Current Fault.

Your cart contains: 10 Item(s)
Subtotal: $4,442.47 View - Checkout >>
Acceptance Mark

Customer Account: